FV10D/4-275S
UN:220/380V UC:275V In:10kA Imax:20kA Uoc:20kV Up≤1.2kV |
Coding of ac surge protector FV10D/4-275S

Dimension of ac surge protector FV10D/4-275S

Circuit of ac surge protector FV10D/4-275S

Installation of ac surge protector FV10D/4-275S



-Consisting of a base part and MOV pluggable protection modules.
-For using in the lightning protection zones concept at boundary 1-2.
-The core parts are metal oxide vristor components with high discharge capacity.
-Low residual voltage and quick response.
-Reliable control thanks to Thermo Dynamic Control disconnector.
-With remote signaling contact for control device.
-Fault indication via red mark in the inspection window.
-Protection mode: L1,L2,L3,N-PE.
![]() |
FV10D/4-275S
UN:220/380V UC:275V In:10kA Imax:20kA Uoc:20kV Up≤1.2kV |
Coding of ac surge protector FV10D/4-275S

Dimension of ac surge protector FV10D/4-275S

Circuit of ac surge protector FV10D/4-275S

Installation of ac surge protector FV10D/4-275S



| Model. No. | FV10D/4-275(S) |
| Test class IEC/EN/VDE | Class II+III/C+D/T2+T3 |
| Type of Network | TT ,TN |
| Protection Mode | L1,L2,L3,N-PE |
| Nominalvoltage 50(60)Hz UN | 220/380V |
| Rated Voltage (Max. Cont. Operating Voltage) Uc | 275V |
| Max. discharge current (8/20us)Imax | 20kA |
| Nominal discharge current (8/20us) IN | 10kA |
| Voltage protective level Up | ≤1.2kV |
| Open circuit voltage Uoc | 20kV |
| Response time tA | ≤25ns |
| Recommended back-up fuse | 63A |
| Isolation resistance | >102MΩ |
| I/O Connections | Multi core wire:4mm2~25mm2 |
| Mounting | 35mm Symmetrical rail(EN50022-DIN46277-3) |
| Operation temperature range/humidity /altitude | -40°C~+80°C / 30%~90% / 3000m |
| Degree of protection | IP20 |
| Housing material | UL94V-0 |
| Disconnectionindicator | Mechanical indicator (Green: OK, Red: replace) |
| Remote controlcontact | Optional |
MOQ is flexible and can be negotiated. Depending on your system solution, Accept Customization for Small Orders. Design products as your specification. Professional protection and stable performance for global projects. Submit an online message. Reply within 24 hours by email.
FATECH supplies products to global customers through distributors, wholesalers, and direct project cooperation. You can contact us online for quotation and support.
The remote signaling contact monitors the working status of the SPD. It sends an alarm signal when the SPD fails or needs replacement, enabling real-time monitoring and maintenance.
FATECH SPDs feature TUV & CE certification, stable performance, long service life, and professional technical support. They are widely used in PV, industrial, lighting, network, and residential applications with high cost-performance.
Yes, we support OEM and ODM services
SPDs are widely used in residential buildings, commercial centers, industrial factories, solar PV power stations, LED lighting, security CCTV, telecom base stations, data centers, and infrastructure projects.
Effective grounding provides a low-resistance path for surge current to discharge quickly. Poor grounding will reduce protection performance, increase residual voltage, and may cause equipment damage.