FLP03 6kV outdoor surge arrester

FLP03
FATECH FLP03 series, including FLP03-150-P/G, FLP03-150-S/G, FLP03-275-P/G, FLP03-275-S/G, FLP03-320-P/G, FLP03-320-S/G, FLP03-385-P/G and FLP03-385-S/G, are Class II+III/C+D/T2+T3 combined surge protective devices developed for LED street light systems.
Suitable for 120V, 230V and 380V LED street light power supply networks, this series offers continuous operating voltages of 150V, 275V, 320V and 385V. It features maximum discharge current 6kA and nominal discharge current 3kA, providing graded voltage protection levels for L-N, N-PE and L-PE circuits to effectively suppress transient surge overvoltage.
It achieves fast response time of ≤25ns for L-N and ≤100ns for N-PE, with a recommended backup fuse of 16A. Different from other models, this version is designed without internal thermal cut-off member, adopting basic three-loop protection mode for cost-effective conventional surge protection.
With IP66 high waterproof and dustproof grade, UL94V-0 flame retardant housing, wide operating temperature range from -40°C to +80°C and applicable altitude up to 3000m, it is economical and durable, ideal for general municipal LED street lighting, outdoor lamps and cost-sensitive lightning protection projects.

-New designed LED series connected surge protection module for lighting, without LED failure indicator.

-specifically for outdoor and commercial LED lighting applications, LED signage and traffic light manufacturers,including roadway lighting, parking garage lighting, washwall lighting, traffic lighting, flood lighting, digital signage,street lightning, and tunneal lighting.

-Imax 6kA lightning surge protection.

-Metal oxide varistor (MOV) thermal protection.

-Parallel connected and series connected SPD options.

-Waterproof IP66.-

Advantage

Stable & Reliable Surge Protection

Stable & Reliable Surge Protection

Adopts high-quality core components and precise circuit design, providing stable and consistent performance to effectively suppress lightning surges and transient overvoltage, ensuring long-term safe operation of equipment.
Adopts high-quality core components and precise circuit design, providing stable and consistent performance to effectively suppress lightning surges and transient overvoltage, ensuring long-term safe operation of equipment.

Adopts high-quality core components and precise circuit design, providing stable and consistent performance to effectively suppress lightning surges and transient overvoltage, ensuring long-term safe operation of equipment.

Covers AC, DC, photovoltaic, PoE network, and signal surge protection solutions, widely used in solar systems, LED lighting, industrial control, security monitoring, buildings and infrastructure.
Durable Structure & Easy Installation

Durable Structure & Easy Installation

Durable Structure & Easy Installation
Certified Quality & Cost-Effective

Certified Quality & Cost-Effective

Most core products have passed TUV, CE and international safety certifications, with strict quality control. Stable performance and reasonable pricing bring high cost-performance for global projects.

FLP03-150-P/G

FLP03-150-S/G

UN : 120V

UC : 150V

Imax:6kA

In:3kA

FLP03-275-P/G

FLP03-275-S/G

UN : 230V

UC : 275V

Imax:6kA

In:3kA

FLP03-320-P/G

FLP03-320-S/G

UN : 230V

UC : 320V

Imax:6kA

In:3kA

FLP03-385-P/G

FLP03-385-S/G

UN : 380V

UC : 385V

Imax:6kA

In:3kA

Coding of FLP03

Dimension of  FLP03

Circuit of FLP03

Electrical parameters

Model. No. FLP03-150-P/G
FLP03-150-S/G
FLP03-275-P/G
FLP03-275-S/G
FLP03-320-P/G
FLP03-320-S/G
FLP03-385-P/G
FLP03-385-S/G
Test class IEC/EN/VDE Class II+III/C+D/T2 T3
Type of Network LED street light
Nominal voltage 50(60)Hz UN 120V 230V 230V 380V
Rated Voltage (Max. Cont. Operating Voltage) Uc 150V 275V 320V 385V
Max. discharge current (8/20us)Imax 6kA
Nominal discharge current (8/20us) In 3kA
Voltage protective level Up L-N ≤0.8kV ≤1.1kV ≤1.3kV ≤1.5kV
N-PE ≤0.5kV ≤0.5kV ≤0.6kV ≤1.0kV
L-PE ≤1.0kV ≤1.3kV ≤1.5kV ≤1.7kV
Open circuit voltage Uoc 6kV
Response time tA L-N:≤25ns,N-PE:≤100ns
Recommended back-up fuse 16A
Thermal Cut-off Member No
Protection Mode L-N,N-PE,L-PE
Operation temperature range/altitude -40°C~+80°C /3000m
Degree of protection IP66
Housing material UL94V-0

Searching For A Reliable SPD & Surge Protector To Secure Your Projects?

MOQ is flexible and can be negotiated. Depending on your system solution, Accept Customization for Small Orders. Design products as your specification. Professional protection and stable performance for global projects. Submit an online message. Reply within 24 hours by email.

Why Send Us An Inquiry?

  • Professional SPD & lightning surge protection solutions
  • Custom design for your project & small MOQ supported
  • Certified quality & factory direct price
  • Quick technical support & quotation
  • Response in 24 hours