FV10D/2-275S
UN:220/380V UC:275V In:10kA Iimp:20kA Up≤1.2kV |
1.Coding

2. Dimension

3. Circuit

4. Electrical parameters
| Model. No. | FV10D/2-275(S) |
| Test class IEC/EN/VDE | Class II+III/C+/T2+T3 |
| Type of Network | TT ,TN |
| Protection Mode | L-PE , N-PE |
| Nominalvoltage 50(60)Hz UN | 220/380V |
| Rated Voltage (Max. Cont. Operating Voltage) Ue | 275V |
| Max. discharge current (8/20us)Imax | 20kA |
| Nominal discharge current (8/20us) IN | 10kA |
| Voltage protective level Up | ≤1.2kV |
| Open circuit voltage Uoc | 20kV |
| Response time tA | ≤25ns |
| Recommended back-up fuse | 63A |
| Isolation resistance | >102MΩ |
| I/O Connections | Multi core wire:4mm2~25mm2 |
| Mounting | 35mm Symmetrical rail(EN50022-DIN46277-3) |
| Operation temperature range/humidity /altitude | -40°C~+80°C / 30%~90% / 3000m |
| Degree of protection | IP20 |
| Housing material | UL94V-0 |
| Disconnectionindicator | Mechanical indicator (Green: OK, Red: replace) |
| Remote controlcontact | Optional |
5. Installation